Hi
We're moving a lot of our sites to straight DC.
On a couple of sites we are still using Ceragon IP10's.
These have an IDU that we are currently powered up with a Meanwell power adapter which runs off AC mains power.
The IDU takes -48V.
Is it safe to power the IDU with CAT5 from the Netonix?
I've made a test cable by tying off the 4 pairs (pos: 1,2,4,5 neg:3,6,7,8) and it's reading the expected 48V.
Just want to make sure I'm not missing anything obvious by doing this - anything to watch out for?
thanks
colin
Power IP10 IDU through Netonix
- colinhowlin
- Member
- Posts: 46
- Joined: Wed Feb 17, 2016 10:00 am
- Location: Ireland
- Has thanked: 2 times
- Been thanked: 2 times
-
Dave - Employee
- Posts: 726
- Joined: Tue Apr 08, 2014 6:28 pm
- Has thanked: 1 time
- Been thanked: 158 times
Re: Power IP10 IDU through Netonix
Colin
It's hard for me to say if this is ok. Out POE ground is bonded to our negative power input on our DC switches. So a lot of it depends on if anywhere in
your system, the + battery power gets tied to the chassis ground anywhere. If it does you can't use our present family of DC switches.
Dave
It's hard for me to say if this is ok. Out POE ground is bonded to our negative power input on our DC switches. So a lot of it depends on if anywhere in
your system, the + battery power gets tied to the chassis ground anywhere. If it does you can't use our present family of DC switches.
Dave
- colinhowlin
- Member
- Posts: 46
- Joined: Wed Feb 17, 2016 10:00 am
- Location: Ireland
- Has thanked: 2 times
- Been thanked: 2 times
Re: Power IP10 IDU through Netonix
Hmm, ok.
I can just run it off our DC supply anyway, would have just made my life easier if I could power it off the Netonix!
Is there an adapter you can get that will make this possible?
I can just run it off our DC supply anyway, would have just made my life easier if I could power it off the Netonix!
Is there an adapter you can get that will make this possible?
-
Dave - Employee
- Posts: 726
- Joined: Tue Apr 08, 2014 6:28 pm
- Has thanked: 1 time
- Been thanked: 158 times
Re: Power IP10 IDU through Netonix
don't have an adapter I can recommend.
We are however, coming out with a series of isolated supplies in the future, meant for telecom -48 volt sites.
We are however, coming out with a series of isolated supplies in the future, meant for telecom -48 volt sites.